Animations 3D sweep of temperature through room (X and Y sweep also available).

This example shows the effect of CRAC failure in a room with two cold aisles and one cold aisle (central one) contained.

Highest Inlet Temperature in Racks increases from 28 deg C (left image - all CRACS running) to 32 deg C (right image - single CRAC failure).

             

Animation showing path of air from racks (pathlines from CRAC units under floor also available).

In this example it is possible to identify short circuiting air as the possible reasons for the hot spots.